Notes |
Date |
Text |
2023-01-31 07:18:53 | 2ND GAS REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED | | COMBUSTION AIR FOR THE TANKLESS WATER HEATER IN THE | | GARAGE. THE CALCULATIONS FOR AN 18'X22'X(9'?) GARAGE | | GIVES 3564 CU.FT., FOR A 180,000 BTU HEATER ONLY GIVES | | 20 CU.FT. OF AIR FOR COMBUSTION. IT IS REQUIRED TO HAVE | | 50 CU.FT. PER 1000 BTU. PLEASE PROVIDE MAKEUP AIR OR | | PULL THE COMBUSTION AIR FROM OUTSIDE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|