Plan Review Notes
Plan Review Notes For Permit 23011358
Permit Number 23011358
Review Stop G
Sequence Number 2
Notes
Date Text
2023-01-31 07:18:532ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED
 COMBUSTION AIR FOR THE TANKLESS WATER HEATER IN THE
 GARAGE. THE CALCULATIONS FOR AN 18'X22'X(9'?) GARAGE
 GIVES 3564 CU.FT., FOR A 180,000 BTU HEATER ONLY GIVES
 20 CU.FT. OF AIR FOR COMBUSTION. IT IS REQUIRED TO HAVE
 50 CU.FT. PER 1000 BTU. PLEASE PROVIDE MAKEUP AIR OR
 PULL THE COMBUSTION AIR FROM OUTSIDE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  