2023-01-30 07:23:461ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2407.1 - WHEN THE WATER HEATER IS IN AN
 INTERIOR LOCATION, YOU'LL NEED TO SHOW THE VENTING
 SPECS FOR THE APPLIANCE. INCLUDE THE TERMINATION POINT
 ON THE OUTSIDE OF THE HOUSE WITH THE REQUIRED
 SEPARATION FROM THE OPENINGS INTO THE BUILDING. IF THE
 COMBUSTION AIR FROM THE APPLIANCE IS NOT BEING TAKEN
 FROM THE OUTSIDE, YOU'LL NEED TO DETAIL THE VENTING
 REQUIREMENTS TO THE ROOM/COMPARTMENT THAT THE APPLIANCE
 IS IN.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  