2023-02-10 22:37:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LOAD CALC IS INCORRECT. NO LOAD SHOWN FOR SQUARE |
| FOOTAGE VA, NO LOAD SHOWN FOR CAR CHARGER. PROVIDE |
| ACCURATE LOAD CALC. NEC 220 FBC 107.2.1 |
| |
| 2. PROVIDE NOTE ON PLAN THAT STATES GENERATOR WILL |
| REQUIRE SEPARATE PERMIT AND PLANS SUBMITTALS. FBC 105.1 |
| |
| 3. EQUIPMENT GROUND SHOWN FROM METER CAN TO SERVICE |
| RATED ATS. THIS IS NOT PERMITTED. NEC 250.24C |
| |
| 4. SMOKE/CO ALARMS NOT SHOWN OUTSIDE SLEEPING ROOM |
| DOORS WITHIN 10 FEET PER FBC-R 314 AND 314 AND NFPA72 |
| |
| 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |