Plan Review Notes For Permit 23011312 |
Permit Number |
23011312 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-03 13:20:14 | 1ST GAS REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED | | COMBUSTION AIR CALCULATIONS FOR THE RANGE AND | | FIREPLACE. | | | | 2. 2020 FRC R303.5.1 - RESIDENTIAL GAS GENERATORS MUST | | BE 10 FEET FROM OPENINGS. PLEASE SHOW A DISTANCE TO THE | | OPENING INTO THE STRUCTURE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|