Plan Review Notes
Plan Review Notes For Permit 23011312
Permit Number 23011312
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-15 15:35:51NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC R401.4
  
 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE OVERHEAD GARAGE DOOR -
  
 3) PLEASE PROVIDE THE INSTALLATION INSTRUCTIONS WHICH
 ARE PART OF THE PRODUCT APPROVAL FOR THE ROOFING TILE -
 PLEASE CIRCLE THE ROOF TILE ATTACHMENTS TO BE USED IN
 THE PRODUCT APPROVAL - IF USING ADHESIVE FOR ATTACHMENT
 PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE ADHESIVE.
  
 4) PLEASE SHOW THE EXTERIOR WINDOW/DOOR FLASHING DETAIL
 PER FBC R703.4
  
 5) PLEASE PROVIDE THE DOCUMENTATION FOR THE FOAM SPRAY
 INSULATION - FBC R316.3 SURFACE BURNING
 CHARACTERISTICS.
 UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM
 PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN
 MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND
 SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
 6) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING
 BUILDING DEMOLITION, RETAINING WALLS, POOL, FENCE,
 DRIVEWAY
  