Plan Review Notes
Plan Review Notes For Permit 23011306
Permit Number 23011306
Review Stop M
Sequence Number 2
Notes
Date Text
2023-04-05 12:20:13PLAN DENIED
 REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS.
 2020 FLORIDA ENERGY CODE. NEED AUTOMATIC
 DAMPERS ON FRESH AIR DUCT.
  
 REFER TO SECTIOIN 607.5.5 SHAFT ENCLOSURES 2020FBC (M)
 NEED FIRE SMOKE DAMPER AT SHAFT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  