 2ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23011265
 3/23/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET S1.0: THE GAS RISER IS INCOMPLETE. PROVIDE THE
 PRESSURE AT THE METER- 2PSI OR 11-INCHES W.C.?
 BASED ON THE LOW PRESSURE TABLE G2413.4(3) FBC RES THE
 ??-INCH COPPER FOR A SYSTEM WITH A 35 FT. TOTAL
 DEVELOPED LENGTH IS LIMITED TO MAXIMUM SUPPLY OF
 131,000 BTU. THE PIPE SHALL BE INCREASED TO 1-INCH FROM
 THE METER TO THE WATER HEATER RISER CONNECTION POINT.
 A) PLEASE LABEL THE PIPING AS UNDERGROUND OR
 ABOVEGROUND- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  