Plan Review Notes For Permit 23011265 |
Permit Number |
23011265 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-03-24 10:54:10 | | | 2ND REVIEW FBC-2020 RES. GAS | | PERMIT- 23011265 | | 3/23/2023 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET S1.0: THE GAS RISER IS INCOMPLETE. PROVIDE THE | | PRESSURE AT THE METER- 2PSI OR 11-INCHES W.C.? | | BASED ON THE LOW PRESSURE TABLE G2413.4(3) FBC RES THE | | ??-INCH COPPER FOR A SYSTEM WITH A 35 FT. TOTAL | | DEVELOPED LENGTH IS LIMITED TO MAXIMUM SUPPLY OF | | 131,000 BTU. THE PIPE SHALL BE INCREASED TO 1-INCH FROM | | THE METER TO THE WATER HEATER RISER CONNECTION POINT. | | A) PLEASE LABEL THE PIPING AS UNDERGROUND OR | | ABOVEGROUND- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|