Plan Review Notes
Plan Review Notes For Permit 23011265
Permit Number 23011265
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-02 12:10:35FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF THE ELECTRICAL PANEL (PANEL
 SCHEDULE), NEW LIGHTING BRANCH CIRCUITS, 240 V EV
 CHARGER OUTLET BRACH CIRCUIT. THIS INFORMATION SHALL
 INCLUDE CONDUCTORS SIZE AND PROTECTION. NEC 220, 240,
 250, 408.4(A)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER