Plan Review Notes
Plan Review Notes For Permit 23011265
Permit Number 23011265
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-17 10:40:35REMODEL/ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SIDING IS SUBJECT TO WIND LOADS - PLEASE SHOW SIDING
 TYPE AND ATTACHMENTS OR PROVIDE A PRODUCT APPROVAL -
 FBC R703.1.2
  
 2) PLEASE SHOW THE SMOKE DETECTOR LOCATIONS - FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.