Plan Review Notes For Permit 23011265 |
Permit Number |
23011265 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-17 10:40:35 | REMODEL/ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) SIDING IS SUBJECT TO WIND LOADS - PLEASE SHOW SIDING | | TYPE AND ATTACHMENTS OR PROVIDE A PRODUCT APPROVAL - | | FBC R703.1.2 | | | | 2) PLEASE SHOW THE SMOKE DETECTOR LOCATIONS - FBC | | R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
|