2023-02-16 12:26:03 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FRC P3107.1 - THE COMMON VENT SERVING THE LAV, |
| BATHTUB, WASHER, AND LAUNDRY TUB IS NON-COMPLIANT. A |
| COMMON VENT CAN ONLY SERVE FIXTURES ON THE SAME FLOOR. |
| |
| 2. 2020 FRC P3201.7 - THE TRAP SIZE SHOWN FOR THE |
| WASING MACHINE IS 1 1/2" AND THE MINIMUM IS 2". |
| |
| 3. 2020 FRC P3107.1 - THE SHOWER UPSTAIRS CANNOT DRAIN |
| DOWN ONTO THE LAVATORY AS EITHER A COMMON VENT. THEY |
| WOULD HAVE TO BE ON THE SAME FLOOR LEVEL. |
| |
| 4. 2020 FRC P3108.2.1 - THE DOWNSTAIRS SHOWER AND WATER |
| CLOSET ARE NOT VENTED TO CODE. ONLY ONE TRAPPED FIXTURE |
| IS ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S |
| CONNECTION TO THE WET VENT. YOU CURRENTLY HAVE 2 |
| UPSTREAM (OF THE LAV THAT IS NOT VENTED CORRECTLY DUE |
| TO THE SHOWER UPSTAIRS). |
| |
| 5. THE KITCHEN SINK IS INCORRECTLY LABELED AS A "LAV". |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |