2023-02-16 12:26:031ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3107.1 - THE COMMON VENT SERVING THE LAV,
 BATHTUB, WASHER, AND LAUNDRY TUB IS NON-COMPLIANT. A
 COMMON VENT CAN ONLY SERVE FIXTURES ON THE SAME FLOOR.
  
 2. 2020 FRC P3201.7 - THE TRAP SIZE SHOWN FOR THE
 WASING MACHINE IS 1 1/2" AND THE MINIMUM IS 2".
  
 3. 2020 FRC P3107.1 - THE SHOWER UPSTAIRS CANNOT DRAIN
 DOWN ONTO THE LAVATORY AS EITHER A COMMON VENT. THEY
 WOULD HAVE TO BE ON THE SAME FLOOR LEVEL.
  
 4. 2020 FRC P3108.2.1 - THE DOWNSTAIRS SHOWER AND WATER
 CLOSET ARE NOT VENTED TO CODE. ONLY ONE TRAPPED FIXTURE
 IS ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S
 CONNECTION TO THE WET VENT. YOU CURRENTLY HAVE 2
 UPSTREAM (OF THE LAV THAT IS NOT VENTED CORRECTLY DUE
 TO THE SHOWER UPSTAIRS).
  
 5. THE KITCHEN SINK IS INCORRECTLY LABELED AS A "LAV".
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved