2023-03-02 09:00:45 | ELECTRIC REVIEW FAILED |
| |
| 1) IT APPEARS ELECTRICAL DRAWINGS ARE INCOMPLETE. NEW |
| FLOOR PLAN DETAILS A KITCHEN, DEN, DINING ROOM, FRONT |
| PORCH AND SECOND FLOOR BATHROOM, AND BEDROOMS ARE TO BE |
| RENOVATED. ELECTRIC PLANS DO NOT DETAIL ALL WIRING THAT |
| WILL BE MODIFIED OR ADDED. IN ADDITION, NOTES STATE |
| THAT ALL EXTERIOR WALLS ARE TO BE INSULATED AND |
| CONDUITS ARE TO BE INSTALLED IN THESE WALLS. PLEASE |
| PROVIDE A COMPLETE ELECTRICAL PLAN AS APPLICABLE. |
| |
| FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL |
| |
| 2) PLEASE PROVIDE AN ELECTRICAL RISER DETAILING ALL |
| EQUIPMENT, CONDUIT, CONDUCTORS, GROUNDING ELECTRODE |
| SYSTEM, AND OVERCURRENT PROTECTION. |
| |
| NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| THE FEEDERS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |