Plan Review Notes For Permit 23011162 |
Permit Number |
23011162 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-07-06 13:34:11 | NEW BUILDING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW ON THE FLOOR PLAN THE NORTH EXTERIOR | | WALL WHICH IS 7' 6" FROM THE PROPERTY LINE TO BE 1 HOUR | | FIRE RATED - FBC TABLE 602 | | | | 2) PLEASE SHOW THE CALCULATIONS FOR THE UNPROTECTED | | OPENINGS IN THE NORTH EXTERIOR WALL WHICH IS 7' 6" FROM | | THE PROPERTY LINES - PER FBC TABLE 705.8 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|