2023-05-09 15:10:39 | IT APPEARS THAT THE MECHAICAL COMMENTS FOR THIS PROJECT |
| GOT MIXED UP WITH ANOTHER PROJECT WHEN YOU RESUBMITTED. |
| PLEASE ADDRESS THE COMMET BELOOW AS THIS PROJECT HAS |
| THE LOBBIES AND VENTILATION ISSUES, NOT THE RATED |
| WALLS. |
| |
| 1ST REVIEW FMC |
| PERMIT: 23011162 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-600: IN THE VENTILATION RATES SCHEDULE THE |
| ROOMS ARE IDENTIFIED AS LOBBY ON BOTH FLOORS. TABLE |
| 403.3.1.1 INDICATES LOBBIES TO BE CALCULATED WITH AN |
| OCCUPANCY DENSITY OF 150 WITH A PERSON CFM OF 7.5 AND |
| THE BREATHING ZONE CFM/SQ FT. OF 0.06. WITH USING |
| LOBBIES FROM TABLE 403.3.1.1 THE OUTDOOR AIR |
| CALCULATION FOR BOTH LOBBIES ARE LOW. PLEASE PROVIDE |
| THE CORRECTED VENTILATION RATES FOR THESE SPACES. FMC |
| 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 2) THESE DRAWINGS INDICATE THAT THIS IS ONLY THE |
| BUILDING SHELL. SHEET T.100 INDICATES THIS DESIGN OF |
| THIS BUILDING IS FOR WORST CASE SCENARIO WHICH IS |
| ASSEMBLY A-2 BUT SHEET M-600 IN THE BASIS OF DESIGN FOR |
| FUTURE TENANTS DOES NOT REFLECT THE OUTDOOR AIR OR |
| EXHAUST REQUIREMENTS FOR THE WORST CASE SCENARIO. |
| EITHER REMOVE ALL COMMENTS AND TABLES FOR THE FUTURE |
| USE OR PROVIDE THE CORRECTED SCHEDULES REQUIRED FOR THE |
| ASSEMBLY A-2 THAT IS STATED ON SHEET T.100. FMC |
| 403.3.1.1; TABLE 403.3.1.1 AND FBC 107.3.5 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |