Date |
Text |
2023-02-02 14:32:20 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE |
| AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE |
| SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR |
| PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . AFTER YOU HAVE THE PERMIT(S) |
| GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| LETTER AND I WILL COMPLY THIS COMMENT. |
| |
| 2. 2020 FPC 607.1.1/613.1 - THE WATER HEATER AT THE |
| JANITOR SINK SHALL HAVE A MIXING VALVE. ALL HOT WATER |
| SHALL BE LIMITED BY SOMETHING OTHER THAN THE THERMOSTAT |
| ON THE WATER HEATER. |
| |
| 3. 2020 FPC 901.2.1 - PROVIDE A VENT FOR THE JANITOR |
| SINK. |
| |
| 4. 2020 FPC 906.1 - IT APPEARS THAT ACCORDING TO TABLE |
| 906.1, YOU NEED AT THE MINIMUM A 3" VENT STACK TO THE |
| DOWNSTAIRS TENANT. 4" DRAINS WITH THAT MANY DFU'S |
| CANNOT BE VENTED OFF OF 2". PLEASE RECALCULATE THE |
| FUTURE VENT SIZING. |
| |
| 5. 2020 FPC 1003.4 - PLEASE SHOW THE OIL ALARM OR OIL |
| SEPARATOR FOR THE SUMP IN THE ELEVATOR SHAFT. |
| |
| 6. 2020 FPC 712.3.2/906.5 - PLEASE DETAIL A VENT FOR |
| THE SUMP PIT. |
| |
| 7. 2020 FPC 606.2 - ADD A SHUT OFF ON THE SUPPLY LINE |
| TO THE HOSE BIB. |
| |
| 8. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE ADD A DETAIL |
| FOR THE SCUPPERS |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |