Plan Review Notes
Plan Review Notes For Permit 23011162
Permit Number 23011162
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-09 16:06:33NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING -
 FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 2) PLEASE PROVIDE A SURVEY
  
 3) DRAWING T.100 UNDER PROJECT DATA - BUILDING SQUARE
 FOOT FOR OCCUPANT LOAD APPEARS TO BE INCORRECT - PLEASE
 CORRECT.
  
 4) DRAWING T.100 STATES THAT A RESTROOM IS PROVIDED - A
 RESTROOM IS NOT SHOWN ON THE PLAN.
  
 5) RISK CATEGORY SHOWN IS "II" - FOR A BUILDING WITH AN
 ASSEMBLY OCCUPANCY OVER 300 WILL BE A RISK CATEGORY III
 WITH WIND DESIGN SPEED OF 180MPH PER FBC TABLE 1604.5
  
 6) PLEASE SHOW THE ADJACENT BUILDING OCCUPANCY
 CLASSIFICATION FBC TABLE 706.4
  
 7) DOORS CANNOT SWING BEYOND THE PROPERTY LINE - FBC
 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO
 THE PUBLIC RIGHT-OF-WAY.
  
 8) PLEASE SHOW THAT THE BUILDING ENTRIES ARE ACCESSIBLE
 - FBC 206.2.1
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE. - 206.2.4
 SPACES AND ELEMENTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY
 WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH
  
 9) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING
 BUILDING DEMO.
  
  