2023-02-09 16:06:33 | NEW BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING - |
| FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| WATER RETAINING SWALES) |
| |
| 2) PLEASE PROVIDE A SURVEY |
| |
| 3) DRAWING T.100 UNDER PROJECT DATA - BUILDING SQUARE |
| FOOT FOR OCCUPANT LOAD APPEARS TO BE INCORRECT - PLEASE |
| CORRECT. |
| |
| 4) DRAWING T.100 STATES THAT A RESTROOM IS PROVIDED - A |
| RESTROOM IS NOT SHOWN ON THE PLAN. |
| |
| 5) RISK CATEGORY SHOWN IS "II" - FOR A BUILDING WITH AN |
| ASSEMBLY OCCUPANCY OVER 300 WILL BE A RISK CATEGORY III |
| WITH WIND DESIGN SPEED OF 180MPH PER FBC TABLE 1604.5 |
| |
| 6) PLEASE SHOW THE ADJACENT BUILDING OCCUPANCY |
| CLASSIFICATION FBC TABLE 706.4 |
| |
| 7) DOORS CANNOT SWING BEYOND THE PROPERTY LINE - FBC |
| 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO |
| THE PUBLIC RIGHT-OF-WAY. |
| |
| 8) PLEASE SHOW THAT THE BUILDING ENTRIES ARE ACCESSIBLE |
| - FBC 206.2.1 |
| AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN |
| THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE |
| PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; |
| AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE |
| BUILDING OR FACILITY ENTRANCE THEY SERVE. - 206.2.4 |
| SPACES AND ELEMENTS. |
| AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE |
| BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE |
| SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY |
| WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH |
| |
| 9) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING |
| BUILDING DEMO. |
| |
| |