Plan Review Notes
Plan Review Notes For Permit 23011136
Permit Number 23011136
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-03 07:02:141ST REVIEW FMC
 PERMIT: 23011136
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-600: SUBMIT ONLY THE INFORMATION THAT IS
 RELEVANT TO TAKING THIS CHANGE OF OCCUPANCY BACK TO A
 SHELL. THERE IS NO LOBBY SHOWN ON THESE SUBMITTED
 DRAWINGS. THERE IS NO 2ND FLOOR, REMOVE THIS FROM THE
 BASIS OF DESIGN ON SHEET M-600. THE SHEET T.100
 INDICATES THIS SPACE IS DESIGNED FOR WORSE CASE WHICH
 IS AN ASSEMBLY A-2. THE INFORMATION ON SHEET M-600
 WOULD NOT WORK, THE SQUARE FOOTAGE SHOWN ON T.100 FOR
 THE KITCHEN AND THE DINING ROOM WOULD REQUIRE A TOTAL
 OF 4,522 CFM???S OF OUTDOOR AIR AND THE KITCHEN WOULD
 REQUIRE 1,881 CFM???S OF EXHAUST. THE BASIS OF DESIGN
 ON M.600 DOES NOT SHOW THIS SO THE ROOF GRAVITY
 VENTILATOR SCHEDULE WOULD NOT WORK. SHEET M-500 SHOULD
 BE REMOVED AS THERE IS NO MECHANICAL SYSTEM SHOWN FOR
 THIS SHELL. FMC 403.3.1.1 AND TABLE 403.3.1.1; FBC
 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  