Date |
Text |
2023-05-24 15:30:41 | DATE: WED. MAY24TH/23 |
| ACTION: PASSED/ BUILDING PROVISO |
| |
| 1) BUILDING PROVISO: SHEET S.002 HAS HEADING DEALING |
| WITH WELDING & STRUCTURAL STEEL FOR THE PROJECT. WELDED |
| OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS EITHER |
| BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| INSPECTION. |
| 2020 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| BRUNELLE AT 561-805-6670. |
| |
| 2) BUILDING PROVISO/ DEFERRED SUBMITTALS/ COMPONENTS & |
| CLADDING. |
| COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND |
| CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 3) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 4) BUILDING PROVISO: DELEGATED ENGINEERING. |
| 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| RECORD FOR REVIEW. |
| |
| 5) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE |
| IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL |
| HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| 5) BUILDING PROVISO: THE STRUCTURAL SHEETS INDICATE THE |
| GENERAL CONTRACTOR SHALL HIRE A LICENSED SHORING |
| ENGINEER TO TEMPORARILY SUPPORT THE EXISTING STRUCTURE. |
| JAMES A. WITMER BN, PX, SFP, CBO/ SENIOR COMMERCIAL |
| COMBINATION PLANS EXAMINER |
| |