Plan Review Notes
Plan Review Notes For Permit 23011125
Permit Number 23011125
Review Stop B
Sequence Number 3
Notes
Date Text
2023-05-26 09:35:39RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011125
 214 LINDA LN
  
 1- REVISE ENGINEER CALCULATIONS SUBMITTED:
 A) THE NAIL FASTENING SPACING SPECIFIED BY THE ENGINEER
 DOESN'T MATCH THE NAIL FASTENING SPACING LISTED IN THE
 NOA 18-0919.12 ON PAGE 55 OF 67 FOR A MAXIMUM DESIGN
 PRESSURES OF -52.5PSF. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 B)THE ROOF ZONES DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER ARE TOO LOW. IT LOOKS LIKE ENGINEER IS USING
 ASCE-7-10 INSTEAD OF CURRENT ASCE-7-16. REVISE AS
 REQUIRED. SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 C)ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR ALL 4
 NEW ROOF ZONES.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 D)ENGINEER TO REVISE THE PERIMETER WIDTH DIMENSION AND
 THE CORNER ZONES DIMENSIONS. SEE ASCE 7-16 AND REVISE
 AS REQUIRED.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]