2023-05-15 11:09:26RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011125
 214 LINDA LN
  
 1- REVISE ENGINEER CALCULATIONS SUBMITTED:
 A) THE NAIL FASTENING SPACING SPECIFIED BY THE ENGINEER
 DOESN'T MATCH THE NAIL FASTENING SPACING LISTED IN THE
 NOA 18-0919.12 ON PAGE 55 OF 67 FOR A MAXIMUM DESIGN
 PRESSURES OF -52.5PSF. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)THE ROOF ZONES DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER ARE TOO LOW. IT LOOKS LIKE ENGINEER IS USING
 ASCE-7-10 INSTEAD OF CURRENT ASCE-7-16. REVISE AS
 REQUIRED. SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 C)ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR ALL 4
 NEW ROOF ZONES.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 D)ENGINEER TO REVISE THE PERIMETER WIDTH DIMENSION AND
 THE CORNER ZONES DIMENSIONS. SEE ASCE 7-16 AND REVISE
 AS REQUIRED.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,