2023-04-04 11:39:58 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA |
| NO.: 18-0919.12 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| USED CORRESPONDING TO ENGINEERS CALCULATIONS. PAGES #1 |
| & #2, INSTALLATION INSTRUCTIONS FOR SYSTEM E (3) |
| PAGE(S) #55 & #56 AND LIMITATIONS PAGE(S) #67. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER; TO CORRECT EXPOSURE |
| CATEGORY, DESIGN PRESSURES & NAILING PATTERNS. THE |
| EXPOSURE CATEGORY FOR 214 LINDA LN WEST PALM BEACH, FL |
| 33405 IS EXPOSURE CATEGORY D. |
| 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN |
| ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |