Plan Review Notes For Permit 23011118 |
Permit Number |
23011118 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-05-05 08:25:32 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) (THE PRODUCT APPROVAL PROVIDED FOR THE FOAM IS FOR A | | FOAM ROOFING SYSTEM THE DRAWINGS SHOW THE ROOFING | | SYSTEM TO BE SHINGLES). PLEASE PROVIDE DOCUMENTATION | | FOR THE SPRAY FOAM INSULATION (ICC - ES EVALUATION | | REPORT) - FBC R316.3 SURFACE BURNING CHARACTERISTICS. | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | |
|