Plan Review Notes For Permit 23011118 |
Permit Number |
23011118 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-04-17 10:13:26 | 3RD PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | | | 2. POOL HOUSE - 2020 FRC P3108.2.1 - THE SHOWER AND | | WATER CLOSET ARE BOTH UPSTREAM OF THE LAVATORY | | CONNECTION. ONLY ONE TRAPPED FIXTURE IS ALLOWED TO BE | | UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE | | HORIZONTAL BRANCH DRAIN BEING WET VENTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|