2023-04-18 15:45:05POOL HOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SEE DRAWING A-1.0 GENERAL NOTE NUMBER 7 - (NOTE
 NUMBER 7 CAN BE CHANGED TO STATE THE SOIL BEARING
 CAPACITY IS 2500 PSF OR MORE) - PLEASE PROVIDE A SOIL
 REPORT (GEOTECHNICAL REPORT) FBC 1803.2
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR -
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 3) A PRODUCT APPROVAL HAS BEEN PROVIDED FOR A SINGLE
 HUNG WINDOW - THE DRAWINGS DO NOT SHOW A LOCATION FOR A
 SINGLE HUNG WINDOW.
  
 4) PRODUCT APPROVAL (FL11136 - R8) FOR THE SWING DOOR
 IS FOR THE 2017 FBC CODE VERSION - YOU NEED TO PROVIDE
 A DOOR PRODUCT APPROVAL FOR THE 2020 FBC CODE VERSION.
  
 5) PLEASE PROVIDE DOCUMENTATION FOR THE SPRAY FOAM
 INSULATION (ICC - ES EVALUATION REPORT) - FBC R316.3
 SURFACE BURNING CHARACTERISTICS.
 UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM
 PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN
 MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND
 SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  