2023-04-18 15:45:05 | POOL HOUSE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) SEE DRAWING A-1.0 GENERAL NOTE NUMBER 7 - (NOTE |
| NUMBER 7 CAN BE CHANGED TO STATE THE SOIL BEARING |
| CAPACITY IS 2500 PSF OR MORE) - PLEASE PROVIDE A SOIL |
| REPORT (GEOTECHNICAL REPORT) FBC 1803.2 |
| |
| 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR - |
| ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB |
| 107.3.4 |
| |
| 3) A PRODUCT APPROVAL HAS BEEN PROVIDED FOR A SINGLE |
| HUNG WINDOW - THE DRAWINGS DO NOT SHOW A LOCATION FOR A |
| SINGLE HUNG WINDOW. |
| |
| 4) PRODUCT APPROVAL (FL11136 - R8) FOR THE SWING DOOR |
| IS FOR THE 2017 FBC CODE VERSION - YOU NEED TO PROVIDE |
| A DOOR PRODUCT APPROVAL FOR THE 2020 FBC CODE VERSION. |
| |
| 5) PLEASE PROVIDE DOCUMENTATION FOR THE SPRAY FOAM |
| INSULATION (ICC - ES EVALUATION REPORT) - FBC R316.3 |
| SURFACE BURNING CHARACTERISTICS. |
| UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM |
| PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN |
| MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION |
| SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND |
| SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 |
| WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY |
| INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| |
| |