Plan Review Notes
Plan Review Notes For Permit 23011118
Permit Number 23011118
Review Stop P
Sequence Number 2
Notes
Date Text
2023-03-07 06:37:382ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. COMMENT NOT ADDRESSED - THE KITCHEN SINK IS NOT A
 BATHROOM GROUP FIXTURE. ONLY BATHROOM GROUP FIXTURES
 ARE ALLOWED TO BE INCLUDED WITHIN THE WET VENT FOR THE
 BATHROOM. THE KITCHEN SINK MUST DISCHARGE DOWNSTREAM OF
 THE LAST BATHROOM GROUP FIXTURE BEING WET VENTED.
 POOL HOUSE DIAGRAM - 2020 FRC P3108.1 - THE KITCHEN
 SINK CANNOT BE THE VENTED FIXTURE THAT CREATES THE WET
 VENT FOR THE BATHROOM GROUP FIXTURES. THE KITCHEN SINK
 WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT
 SYSTEM IF A WET VENT IS USED.
  
 2. ADDITIONAL COMMENT - ADDTION WASTE DIAGRAM - 2020
 FRC P3108.2.1 - THE TUB AND SHOWER ARE BOTH UPSTREAM OF
 THE LAVATORY CONNECTION. ONLY ONE TRAPPED FIXTURE IS
 ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN BEING WET
 VENTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved