2023-03-07 06:37:38 | 2ND PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. COMMENT NOT ADDRESSED - THE KITCHEN SINK IS NOT A |
| BATHROOM GROUP FIXTURE. ONLY BATHROOM GROUP FIXTURES |
| ARE ALLOWED TO BE INCLUDED WITHIN THE WET VENT FOR THE |
| BATHROOM. THE KITCHEN SINK MUST DISCHARGE DOWNSTREAM OF |
| THE LAST BATHROOM GROUP FIXTURE BEING WET VENTED. |
| POOL HOUSE DIAGRAM - 2020 FRC P3108.1 - THE KITCHEN |
| SINK CANNOT BE THE VENTED FIXTURE THAT CREATES THE WET |
| VENT FOR THE BATHROOM GROUP FIXTURES. THE KITCHEN SINK |
| WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT |
| SYSTEM IF A WET VENT IS USED. |
| |
| 2. ADDITIONAL COMMENT - ADDTION WASTE DIAGRAM - 2020 |
| FRC P3108.2.1 - THE TUB AND SHOWER ARE BOTH UPSTREAM OF |
| THE LAVATORY CONNECTION. ONLY ONE TRAPPED FIXTURE IS |
| ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S |
| CONNECTION TO THE HORIZONTAL BRANCH DRAIN BEING WET |
| VENTED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |