Plan Review Notes For Permit 23011118 |
Permit Number |
23011118 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-03 13:04:21 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE LOAD CALCULATION AND PANEL SCHEDULE OF THE | | MAIL PANEL OR MAIL LOAD CENTER INCLUDING INCLUDING | | ADDITION AND POOL HOUSE. NEC 220.82, 408.4(A) | | 2. PROVIDE INFORMATION OF THE SERVICE CONDUCTORS, | | GROUNDED CONDUCTORS, AND PROTECTIONS. NEC 230, 240, 250 | | 3. PROVIDE INFORMATION OF THE FEEDERS FOR SUBPANEL "A" | | (INCLUDING CONDUCTORS SIZES AND EGC). NEC 220, 310.15, | | 250.122 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|