Plan Review Notes
Plan Review Notes For Permit 23011118
Permit Number 23011118
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-03 13:04:21FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION AND PANEL SCHEDULE OF THE
 MAIL PANEL OR MAIL LOAD CENTER INCLUDING INCLUDING
 ADDITION AND POOL HOUSE. NEC 220.82, 408.4(A)
 2. PROVIDE INFORMATION OF THE SERVICE CONDUCTORS,
 GROUNDED CONDUCTORS, AND PROTECTIONS. NEC 230, 240, 250
 3. PROVIDE INFORMATION OF THE FEEDERS FOR SUBPANEL "A"
 (INCLUDING CONDUCTORS SIZES AND EGC). NEC 220, 310.15,
 250.122
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  