2023-01-24 11:12:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | FLOOR SOUND BARRIER UNDERLAYMENT, BUT NO SPEC SHEET NOR | | A PRODUCT NAME FOR THE ACTUAL PROPOSED LAMINATE | | FLOORING. | | | | LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD BUT | | NOT ALL ARE TESTED AND MEETING LISTED AND NFPA | | STANDARDS. | | | | PER NFPA 101, CH 30 | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | ACCORDANCE WITH | | SECTION 10.2. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LAMINATE | | FLOORING PRODUCT NAME AND THE PRODUCT SPEC SHEETS | | INDICATING THE FIRE BEHAVIOR RATING. | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|