Plan Review Notes For Permit 23011060 |
Permit Number |
23011060 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-15 08:25:23 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE PANEL SCHEDULE SHOWING NEW EQUIPMENT OR | | CIRCUITS BEEN POWERED FROM IN ACCORDANCE WITH NEC | | 408.4(A). | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|