2023-01-26 11:00:331ST REVIEW FMC
 PERMIT: 23010960
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IF THIS CHANGE IS FOR THE R-1 UNITS, CLEARLY LABEL
 THESE SHEETS AS SUCH.
  
 2) PROVIDE THE DESIGN THAT SHOWS CODE COMPLIANCE FOR
 THE CONTROLS OF THIS R-1 MECHANICAL SYSTEM . FEC
 C403.2.4.8
  
 3) SHEET M3-16: EXPLAIN THE EXISTING 4 INCH DUCT
 RUNNING ALONG SIDE THE BATH EXHAUST DUCT AND
 TERMINATING OUTDOORS. IT APPEARS THAT IN THE EXISTING
 DRAWING IT IS FOR ANOTHER BATH EXHAUST FAN THAT IS NOT
 SHOWN IN THE PROPOSED PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  