2023-01-26 11:39:07REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A3-00A - PLEASE SHOW THE DIMENSION FOR THE
 REQUIRED TOE CLEARANCE AT THE BAR - FBC A 306.2.3
 MINIMUM REQUIRED DEPTH.
 WHERE TOE CLEARANCE IS REQUIRED AT AN ELEMENT AS PART
 OF A CLEAR FLOOR SPACE, THE TOE CLEARANCE SHALL EXTEND
 17 INCHES (430 MM) MINIMUM UNDER THE ELEMENT.