Date |
Text |
2023-01-25 09:37:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS NO INDICATION OF A SITE PLAN SHOWING THE |
| PROPOSED LOCATIONS OF THE TENTS |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE PROVIDE A SITE PLAN. |
| |
| |
| |
| 2) PLEASE PROVIDE THE TYPE OF EVENT AND IF TABLES AND |
| CHAIRS ARE PROPOSED PLEASE PROVIDE THAT FLOOR PLAN. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| |
| |
| |
| 3) PLEASE ENSURE THE TENTS ARE A MIN. 10 FT. FROM |
| BUILDING OR OTHER TENT STAKES LINES. |
| |
| NO COOKING, BBQS, OPEN FLAMES NOR PROPANE HEATERS UNDER |
| THE TENTS |
| |
| PER NFPA 1 CH 25 |
| |
| 25.2.3 LOCATION AND SPACING. |
| 25.2.3.1 THERE SHALL BE A MINIMUM OF 10 FT (3050 MM) |
| BETWEEN STAKE LINES. [101: 11.11.3.1] |
| |
| 25.2.3.5 THE PLACEMENT OF TENTS RELATIVE TO OTHER |
| STRUCTURES |
| SHALL BE AT THE DISCRETION OF THE AHJ, WITH |
| CONSIDERATION GIVEN |
| TO OCCUPANCY, USE, OPENING, EXPOSURE, AND OTHER SIMILAR |
| FAC TORS. [101: 11.11.3.5] |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE EOF |
| ACKNOWLEDGMENT. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |