Plan Review Notes
Plan Review Notes For Permit 23010901
Permit Number 23010901
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-25 17:29:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010901
 1/25/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-1 & EP-1: THE SANITARY RISER SHOWS A
 VENT-TO-RIDGE ABOVE THE NEW HAND SINK WHICH DOES NOT
 APPEAR TO BE CORRECT GIVEN THE NEW SINK IS ADJACENT TO
 A HALF-WALL AND BAR COUNTER WHICH WOULD PROVIDE NO
 MEANS OF CONCEALING THE VENT PIPE RUN THROUGH THE OPEN
 AIR TO THE ROOF. PLEASE CLARIFY IF THIS IS THE DESIGN
 INTENTION OR A DESIGN ERROR- SEC. 107.2.1 WPB.
  
 2) EP-1: A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR AND DUE TO A CHANGE IN PROCESS, THE
 PLUMBING REVIEW CANNOT BE APPROVED UNTIL AT A MINIMUM
 AN APPLICATION IS SUBMITTED.
  
 GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN
 SUBMIT AN APPLICATION ???TBD??? (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 3) EP1: THE GREASE INTERCEPTOR SHALL ALSO BE REVIEWED
 UNDER THIS MASTER PERMIT. PLEASE PROVIDE THE FOLLOWING
 ITEMS.
 A) MANUFACTURER'S SPECIFICATIONS- SECS.1003.3.5 OR
 1003.3.7 FBC P.
 B) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL AND
 CAPACITY OF THE UNIT.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) REVISE THE ISOMETRIC DRAWING OR PROVIDE AN ENLARGED
 INTERCEPTOR PIPING DIAGRAM. THE DIAGRAM SHALL SHOW THE
 LOCATIONS AND SIZES OF INLETS, OUTLETS, VENTS,
 CLEANOUTS, AND FLOW CONTROL VENTING WHERE REQUIRED BY
 THE MANUFACTURER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  