2023-01-25 17:29:09 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23010901 |
| 1/25/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A-1 & EP-1: THE SANITARY RISER SHOWS A |
| VENT-TO-RIDGE ABOVE THE NEW HAND SINK WHICH DOES NOT |
| APPEAR TO BE CORRECT GIVEN THE NEW SINK IS ADJACENT TO |
| A HALF-WALL AND BAR COUNTER WHICH WOULD PROVIDE NO |
| MEANS OF CONCEALING THE VENT PIPE RUN THROUGH THE OPEN |
| AIR TO THE ROOF. PLEASE CLARIFY IF THIS IS THE DESIGN |
| INTENTION OR A DESIGN ERROR- SEC. 107.2.1 WPB. |
| |
| 2) EP-1: A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| INTERCEPTOR AND DUE TO A CHANGE IN PROCESS, THE |
| PLUMBING REVIEW CANNOT BE APPROVED UNTIL AT A MINIMUM |
| AN APPLICATION IS SUBMITTED. |
| |
| GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED |
| PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN |
| SUBMIT AN APPLICATION ???TBD??? (TO BE DETERMINED) IF |
| YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| COMPLETED PERMIT APPLICATION TO [email protected] |
| . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| TO PASS. |
| |
| 3) EP1: THE GREASE INTERCEPTOR SHALL ALSO BE REVIEWED |
| UNDER THIS MASTER PERMIT. PLEASE PROVIDE THE FOLLOWING |
| ITEMS. |
| A) MANUFACTURER'S SPECIFICATIONS- SECS.1003.3.5 OR |
| 1003.3.7 FBC P. |
| B) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL AND |
| CAPACITY OF THE UNIT. |
| C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| FOR GRAVITY TYPES. |
| D) REVISE THE ISOMETRIC DRAWING OR PROVIDE AN ENLARGED |
| INTERCEPTOR PIPING DIAGRAM. THE DIAGRAM SHALL SHOW THE |
| LOCATIONS AND SIZES OF INLETS, OUTLETS, VENTS, |
| CLEANOUTS, AND FLOW CONTROL VENTING WHERE REQUIRED BY |
| THE MANUFACTURER. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |