Plan Review Notes
Plan Review Notes For Permit 23010901
Permit Number 23010901
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-01-23 14:25:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CVR - THERE IS AN INDICATION WITHIN THE CODE
 RESEARCH AREA OF BUSINESS OCCUPANCY.
  
 PER THE SUBMITTED CONSTRUCTION PLAN SHEETS THE
 OCCUPANCY IS AN ASSEMBLY OCCUPANCY PER NFPA 101 AND
 SHALL COMPLY WITH THAT CODE.
  
 3.3.196.2* ASSEMBLY OCCUPANCY. AN OCCUPANCY (1) USED
 FOR A
 GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP, ENTERTAIN MENT, EATING, DRINKING, AMUSEMENT,
 AWAITING TRANSPORTATION, OR
 SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT
 BUILDING, REGARDLESS OF OCCUPANT LOAD. (SAF-AXM)
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET CVR - THERE IS AN INDICATION WITHIN THE CODE
 RESEARCH AREA OF EGRESS WIDTH AND 1 EXIT REQUIRED, I
 EXIT PROVIDED.
  
 PER THE SUBMITTED CONSTRUCTION PLAN SHEETS THERE ARE
 MULTIPLE EXITS PROVIDED AND PER NFPA 101 CH 12,
 ASSEMBLY OCCUPANCIES, MORE THAN 1 EXIT IS REQUIRED.
  
 12.2.4* NUMBER OF MEANS OF EGRESS
  
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY OCCUPANCIES
 IN ACCORDANCE WITH 12.2.4.4
  
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE,
 STORY, OR PORTION THEREOF SHALL BE NOT LESS THAN TWO,
 EXCEPT UNDER ONE OF
 THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN
 CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR
 BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS OF
 CHAP TERS 11 THROUGH 43 ARE MET.
  
 CH 12 DOES NOT PROVIDE AN EXCEPTION FOR 1 EXIT.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 2 - THERE IS AN INDICATION OF A NEW BAR AS
 WELL AS AN AREA INDICATED AS DJ.
  
 PLEASE PROVIDE A CLEAR NARRATIVE OF WHAT THE THIS
 OCCUPANCY WILL FUNCTION AS, HOURS OF OPERATION, SPECIAL
 EVENT DETAILS, DANCE FLOOR AREA, ETC.
  
  
 4) SHEET A 2 - THE PROPOSED CONSTRUCTION PLAN MAY
 REQUIRE A FIRE ALARM AND FIRE SPRINKLER SYSTEM IF THE
 NARRATIVE AND BUSINESS MODEL OF THIS OCCUPANCY IS A
 "NIGHTCLUB".
  
 12.3.5 EXTINGUISHMENT REQUIREMENTS.
 12.3.5.1 THE FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE
 PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 DEFINITION OF NIGHTCLUB
  
 : A PLACE OF ENTERTAINMENT OPEN AT NIGHT USUALLY
 SERVING FOOD AND LIQUOR AND PROVIDING MUSIC AND SPACE
 FOR DANCING AND OFTEN HAVING A FLOOR SHOW
  
 A FIRE ALARM WILL BE REQUIRED TO MONITOR THE FIRE
 SPRINKLER SYSTEM.
  
 PLEASE EVIEW AND PROVIDE THE APPLICABLE FA & FS
 DOCUMENTS.
  
  
  
 5) SHEET A 1 & A 2 - THERE AE NO INDICATIONS OF A DOOR
 SCHEDULE NOR THE TYPE OF LOCKS/LATCHES ON THE EXIT
 DOORS.
  
 PER NFPA 101 CH 12 & CH 7 MEANS OF EGRESS -
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE WITH
 THE REQUIREMENTS.
  
  
 6) SHEET A 1 & A 2 - THERE IS AN INDICATION OF A REAR
 PATIO AS WELLAS THE REAR EXIT DOUBLE DOOR THAT LEADS TO
 THE REAR PATIO.
  
 EXIT DISCHARGE IS REQUIRED TO LEAD TO A PUBLIC WAY.
  
 12.2.7 DISCHARGE FROM EXITS.
 12.2.7.1 EXIT DISCHARGE SHALL COMPLY WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4
  
 PLEASE PROVIDE DETAILS OF THE PATIO THAT LEADS TO A
 PUBLIC WAY INCLUDING ANY PROPOSED USE OF THE PATIO,
 SEATING PLANS, GATES/FENCING, DIMENSIONS, LIGHTING,
 CANOPIES, ETC.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  