2023-02-02 13:32:32FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW INFORMATION ON THE PANEL SCHEDULE (EXIST.
 PANEL-A) FOR CORRECT RATING OF THE CIRCUIT BREAKERS AND
 BRANCH-CIRCUIT CONDUCTORS SIZE (WATER HEATER, AC UNIT).
 NEC 220, 240, 310.15
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  