Plan Review Notes For Permit 23010901 |
Permit Number |
23010901 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-02 13:32:32 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. REVIEW INFORMATION ON THE PANEL SCHEDULE (EXIST. | | PANEL-A) FOR CORRECT RATING OF THE CIRCUIT BREAKERS AND | | BRANCH-CIRCUIT CONDUCTORS SIZE (WATER HEATER, AC UNIT). | | NEC 220, 240, 310.15 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|