 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, THE ORIENTATION OF STRUCTURE ON PLAN
 SHEETS: A-1/D-1, A-2, & E-1, APPEAR TO BE OPPOSITE OF
 NORTH INDICATER. PLEASE CONFIRM THAT THE ORIENTATION OF
 STRUCTURE ON PLAN SHEETS IS CORRECT AS IS, OR ADJUST
 THE STRUCTURES TO CORRELATE WITH THE DIRECTION
 INDICATER.
 2.) FBC B 303.3 & FBC B 304, COVER SHEET (CODE SECTION)
 STATES THAT THE OCCUPANCY FOR THEIS PROJECT IS B
 (BUSINESS), BUT APPEARS TO BE AN A-2. PLEASE REVIEW AND
 ADJUST OCCUPANCY.
 3.) FBC B 107.2.1 & TABLE FBC B 1004.1.2, THE OCCUPANCY
 LOAD CALCULATIONS ON THE PLAN COVER SHEET INDICATE THE
 DINING AREA TO BE AN ASSEMBLY AREA WITHOUT FIXED SEATS
 (15 S.F. PER PERSON). HOWEVER, THE PLAN SHEET A-1
 INDICATES ASSEMBLY AREA WITH FIXED SEATS OR WITHOUT
 FIXED SEATS CONCENTRATED. PLEASE CLARIFY THE TYPES OF
 ASSEMBLY SEATING ON PLAN SHEET A-1 AND REVIEW/ADJUST
 THE DINING AREA OCCUPANCY/OCCUPANTS ON THE COVERSHEET
 (OCCUPANCY LOAD CALCULATIONS SECTION).
 4.) FBC B TABLE 601/TABLE 705.4, FBC EB 504/505, THE
 ALTERATION LEVEL FROM THE FLORIDA EXISTING BUILDING HAS
 NOT BEEN IDENTIFIED ON THE COVER SHEET. PLEASE IDENTIFY
 THE ALTERATION LEVEL PER THE FLORIDA EXISTING BUILDING
 CODE AND REVIEW TABLE 601 OF THE FLORIDA BUILDING CODE
 AS THE FIRE RATING OF THE DIMIZING WALLS MAY NEED TO BE
 ADJUSTED.
 5.) FBC B 107.2.1 & FBC A 609.4, PLAN SHEET A-2 DETAIL
 4 IS NOT CLEAR AS TO THE HEIGHT REQUIREMENT OF
 ACCESSIBLE GRAB BARS. PLEASE CLARIFY ON THIS DETAIL.
 6.) FBC B 107.2.1 & FBC A 606.3, PLAN SHEET A-2 DETAIL
 3 IS NOT CLEAR AS TO MIRROR HEIGHT REQUIREMENTS AND
 SINK HEIGHT REQUIREMENTS. PLEASE CLARIFY ON THIS
 DETAIL.
 7.) FBC B 107.2.1 & FBC A 902.3, PLAN SHEET A-2 DETAIL
 6 IS NOT CLEAR AS TO ACCESSIBLE COUNTER TOP HEIGHT OF
 34". PLEASE CLARIFY ON THIS DETAIL.
 8.) FBC A 226.2, DISPERSION. DINING SURFACES AND WORK
 SURFACES SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES AND WORK SURFACES.
 PLEASE SHOW ACCESSIBLE SPACES IN EACH REQUIRED AREA.
 9.) FBC B 107.2.1, FBC A 226.2, FBC A 306.2, & FBC A
 306.3. ON PLAN SHEET A-1, THIS LOCATION APPEARS TO BE
 SET BACK IN A CORNER, DOES NOT APPEAR TO HAVE THE
 REQUIRED ACCESS/TURN AROUND SPACE, AND DOES NOT APPEAR
 TO HAVE THE REQUIRED KNEE & TOE SPACE. PLEASE SHOW A
 DIFFERENT LOCATION FOR ACCESSIBLE SPACE AT COUNTER. AND
 SHOW REQUIRED CLEARANCES.
 10.) FBC B 107.2.1, PLEASE PROVIDE
 DETAILS/SPECIFICATIONS FROM MANUFACTURER OF THE THE
 GLUE LAM BEAM PROPOSED ON PLAN SHEET A-1.
 11.) FBC B TABLE 2902.1, THE NUMBER OF PLUMBING
 FIXTURES APPEARS TO BE TOO LOW. PLEASE EVALUATE THE
 MINIMUM NUMBER REQUIRED PER FBC B TABLE 2902.1.