2023-01-23 17:36:31 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II/INSPECTOR |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| 1.) FBC B 107.2.1, THE ORIENTATION OF STRUCTURE ON PLAN |
| SHEETS: A-1/D-1, A-2, & E-1, APPEAR TO BE OPPOSITE OF |
| NORTH INDICATER. PLEASE CONFIRM THAT THE ORIENTATION OF |
| STRUCTURE ON PLAN SHEETS IS CORRECT AS IS, OR ADJUST |
| THE STRUCTURES TO CORRELATE WITH THE DIRECTION |
| INDICATER. |
| 2.) FBC B 303.3 & FBC B 304, COVER SHEET (CODE SECTION) |
| STATES THAT THE OCCUPANCY FOR THEIS PROJECT IS B |
| (BUSINESS), BUT APPEARS TO BE AN A-2. PLEASE REVIEW AND |
| ADJUST OCCUPANCY. |
| 3.) FBC B 107.2.1 & TABLE FBC B 1004.1.2, THE OCCUPANCY |
| LOAD CALCULATIONS ON THE PLAN COVER SHEET INDICATE THE |
| DINING AREA TO BE AN ASSEMBLY AREA WITHOUT FIXED SEATS |
| (15 S.F. PER PERSON). HOWEVER, THE PLAN SHEET A-1 |
| INDICATES ASSEMBLY AREA WITH FIXED SEATS OR WITHOUT |
| FIXED SEATS CONCENTRATED. PLEASE CLARIFY THE TYPES OF |
| ASSEMBLY SEATING ON PLAN SHEET A-1 AND REVIEW/ADJUST |
| THE DINING AREA OCCUPANCY/OCCUPANTS ON THE COVERSHEET |
| (OCCUPANCY LOAD CALCULATIONS SECTION). |
| 4.) FBC B TABLE 601/TABLE 705.4, FBC EB 504/505, THE |
| ALTERATION LEVEL FROM THE FLORIDA EXISTING BUILDING HAS |
| NOT BEEN IDENTIFIED ON THE COVER SHEET. PLEASE IDENTIFY |
| THE ALTERATION LEVEL PER THE FLORIDA EXISTING BUILDING |
| CODE AND REVIEW TABLE 601 OF THE FLORIDA BUILDING CODE |
| AS THE FIRE RATING OF THE DIMIZING WALLS MAY NEED TO BE |
| ADJUSTED. |
| 5.) FBC B 107.2.1 & FBC A 609.4, PLAN SHEET A-2 DETAIL |
| 4 IS NOT CLEAR AS TO THE HEIGHT REQUIREMENT OF |
| ACCESSIBLE GRAB BARS. PLEASE CLARIFY ON THIS DETAIL. |
| 6.) FBC B 107.2.1 & FBC A 606.3, PLAN SHEET A-2 DETAIL |
| 3 IS NOT CLEAR AS TO MIRROR HEIGHT REQUIREMENTS AND |
| SINK HEIGHT REQUIREMENTS. PLEASE CLARIFY ON THIS |
| DETAIL. |
| 7.) FBC B 107.2.1 & FBC A 902.3, PLAN SHEET A-2 DETAIL |
| 6 IS NOT CLEAR AS TO ACCESSIBLE COUNTER TOP HEIGHT OF |
| 34". PLEASE CLARIFY ON THIS DETAIL. |
| 8.) FBC A 226.2, DISPERSION. DINING SURFACES AND WORK |
| SURFACES SHALL BE DISPERSED THROUGHOUT THE SPACE OR |
| FACILITY CONTAINING DINING SURFACES AND WORK SURFACES. |
| PLEASE SHOW ACCESSIBLE SPACES IN EACH REQUIRED AREA. |
| 9.) FBC B 107.2.1, FBC A 226.2, FBC A 306.2, & FBC A |
| 306.3. ON PLAN SHEET A-1, THIS LOCATION APPEARS TO BE |
| SET BACK IN A CORNER, DOES NOT APPEAR TO HAVE THE |
| REQUIRED ACCESS/TURN AROUND SPACE, AND DOES NOT APPEAR |
| TO HAVE THE REQUIRED KNEE & TOE SPACE. PLEASE SHOW A |
| DIFFERENT LOCATION FOR ACCESSIBLE SPACE AT COUNTER. AND |
| SHOW REQUIRED CLEARANCES. |
| 10.) FBC B 107.2.1, PLEASE PROVIDE |
| DETAILS/SPECIFICATIONS FROM MANUFACTURER OF THE THE |
| GLUE LAM BEAM PROPOSED ON PLAN SHEET A-1. |
| 11.) FBC B TABLE 2902.1, THE NUMBER OF PLUMBING |
| FIXTURES APPEARS TO BE TOO LOW. PLEASE EVALUATE THE |
| MINIMUM NUMBER REQUIRED PER FBC B TABLE 2902.1. |