2023-02-15 15:16:29 | 1ST REVIEW FMC |
| PERMIT: |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A SITE DRAWING SHOWING THE GENERATOR ROOM |
| AND THE EXHAUST TERMINATION LOCATION MEETS THE 10 FEET |
| SETBACK FROM PROPERTY LINES. ALSO PROVIDE A DRAWING |
| THAT SHOWS WHERE THE EXTERIOR FILL TANK IS TO BE |
| LOCATED ON THE PROPERTY. FBC 107.3.5 |
| |
| 2) PROVIDE A DETAIL DRAWING SHOWING THE LOCATION OF THE |
| INTAKE LOUVER FOR THE GENERATOR ROOM. THE ORIGINAL |
| APPROVED SHEET A0-101 INDICATES THE WALL THAT THE |
| INTAKE LOUVER IS TO BE INSTALLED IS A 2 HOUR RATED |
| WALL. THIS WALL APPEARS TO BE INSIDE THE FOOTPRINT OF |
| THE BUILDING. THE INTAKE SHOULD BE OUTSIDE OF THE |
| BUILDING. FMC 401.4 |
| |
| 3) SHEET A0-101 OF THE ORIGINAL APPROVED PLANS SHOW THE |
| GENERATOR ROOM HAVING THE TX VAULT ROOM AND THE |
| ELECTRIC ROOM SURROUNDING IT. PROVIDE A DETAIL DRAWING |
| SHOWING THE FUEL PIPING AND TANK VENTILATION LOCATION |
| ON THE EXTERIOR OF THE BUILDING. FBC 107.3.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |