2023-02-15 15:16:291ST REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SITE DRAWING SHOWING THE GENERATOR ROOM
 AND THE EXHAUST TERMINATION LOCATION MEETS THE 10 FEET
 SETBACK FROM PROPERTY LINES. ALSO PROVIDE A DRAWING
 THAT SHOWS WHERE THE EXTERIOR FILL TANK IS TO BE
 LOCATED ON THE PROPERTY. FBC 107.3.5
  
 2) PROVIDE A DETAIL DRAWING SHOWING THE LOCATION OF THE
 INTAKE LOUVER FOR THE GENERATOR ROOM. THE ORIGINAL
 APPROVED SHEET A0-101 INDICATES THE WALL THAT THE
 INTAKE LOUVER IS TO BE INSTALLED IS A 2 HOUR RATED
 WALL. THIS WALL APPEARS TO BE INSIDE THE FOOTPRINT OF
 THE BUILDING. THE INTAKE SHOULD BE OUTSIDE OF THE
 BUILDING. FMC 401.4
  
 3) SHEET A0-101 OF THE ORIGINAL APPROVED PLANS SHOW THE
 GENERATOR ROOM HAVING THE TX VAULT ROOM AND THE
 ELECTRIC ROOM SURROUNDING IT. PROVIDE A DETAIL DRAWING
 SHOWING THE FUEL PIPING AND TANK VENTILATION LOCATION
 ON THE EXTERIOR OF THE BUILDING. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  