2023-03-02 08:44:43ELECTRIC REVIEW FAILED
  
 1) IT APPEARS THE GENERATOR SUBMITTAL SPECIFICATIONS DO
 NO NOT MATCH DRAWING PROVIDE. PLEASE CORRECT AS
 APPLICABLE.
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL
  
 2) PLEASE PROVIDE A CLEAR RISER DETAILING ALL ELECTRIC
 LOADS, EQUIPMENT, CONDUIT, AND CONDUCTORS AND
 OVERCURRENT PROTECTION. PROVIDE A SYMBOL LEGEND FOR ANY
 EQUIPMENT DETAILED WITH ABBREVIATIONS. PLEASE NOTE,
 THAT RISER SHOULD NOT CONFLICT WITH PREVIOUSLY APPROVED
 RISER DIAGRAMS. INDICATE FIRE PUMP WIRING COMPLIES WITH
 ALL RELEVANT NEC CODES, AS PER ARTICLE 695.
  
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER
 DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF
 THE FEEDERS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  