2023-03-02 08:44:43 | ELECTRIC REVIEW FAILED |
| |
| 1) IT APPEARS THE GENERATOR SUBMITTAL SPECIFICATIONS DO |
| NO NOT MATCH DRAWING PROVIDE. PLEASE CORRECT AS |
| APPLICABLE. |
| |
| FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL |
| |
| 2) PLEASE PROVIDE A CLEAR RISER DETAILING ALL ELECTRIC |
| LOADS, EQUIPMENT, CONDUIT, AND CONDUCTORS AND |
| OVERCURRENT PROTECTION. PROVIDE A SYMBOL LEGEND FOR ANY |
| EQUIPMENT DETAILED WITH ABBREVIATIONS. PLEASE NOTE, |
| THAT RISER SHOULD NOT CONFLICT WITH PREVIOUSLY APPROVED |
| RISER DIAGRAMS. INDICATE FIRE PUMP WIRING COMPLIES WITH |
| ALL RELEVANT NEC CODES, AS PER ARTICLE 695. |
| |
| NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| THE FEEDERS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |