2023-02-03 09:25:04FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. ACCORDING TO THE LOAD CALCULATION THE EXISTING 100
 AMP INDOOR PANEL IS UNDERRATED. REVIEW LOAD CALCULATION
 AND UPDATE SERVICE ACCORDING TO THE CALCULATION (FEEDER
 CONDUCTORS FROM 200 AMP MAIN BREAKER METER/MAIN TO
 EXISTING 100 AMP
 INDOOR PANEL). NEC 220.82, 310.15(B)(16)
 [310.15(B)(7)].
  
 2. PROVIDE INFORMATION OF THE SERVICE LATERAL
 (UNDERGROUND SERVICE CONDUCTORS). NEC 230
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  