2023-02-03 09:25:04 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. ACCORDING TO THE LOAD CALCULATION THE EXISTING 100 | | AMP INDOOR PANEL IS UNDERRATED. REVIEW LOAD CALCULATION | | AND UPDATE SERVICE ACCORDING TO THE CALCULATION (FEEDER | | CONDUCTORS FROM 200 AMP MAIN BREAKER METER/MAIN TO | | EXISTING 100 AMP | | INDOOR PANEL). NEC 220.82, 310.15(B)(16) | | [310.15(B)(7)]. | | | | 2. PROVIDE INFORMATION OF THE SERVICE LATERAL | | (UNDERGROUND SERVICE CONDUCTORS). NEC 230 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|