2023-01-23 11:27:12 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL22854-R1 |
| IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM |
| BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT CONSIDER |
| USING FL7473-R9. |
| 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL14317-R13 |
| COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECT |
| ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1 |
| DIRECT-TO-DECK PAGES #4 OR #5. SYSTEM SELECTED MUST |
| MEET OR EXCEED -70 MAXIMUM DESIGN PRESSURE. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE |
| RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP, |
| ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION |
| INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN |
| PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C |
| AREAS. (-70). ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |