2023-02-07 15:02:07 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-23010721 |
| 2/7/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) P101: THE PLAN APPEARS TO BE A COPY AND DOES NOT |
| HAVE A VERIFIABLE ARCHITECT'S SIGNATURE AND SEAL. |
| PLEASE PROVIDE AN ORIGINAL DIGITALLY SIGNED AND SEALED |
| PLAN IN ACCORDANCE WITH FL STATUTE 481.221 AND SEC. |
| 61G1-16.005 FAC. THE CONTRACTOR MAY ALSO SUBMIT HIS OWN |
| PLUMBING PLAN- SEC. 107.2.1 WPB. |
| |
| 2) FAIR HOUSING ACT COMPLIANCE: THE ONE CITY PLAZA |
| CONDOMINIUMS AT 801 S. OLIVE AVE. ARE SUBJECT TO |
| COMPLIANCE WITH FAIR HOUSING ACCESSIBILITY GUIDELINES |
| WHICH CAME INTO EFFECT FOR MULTIFAMILY HOUSING BUILT |
| FOR FIRST OCCUPANCY AFTER MARCH 13, 1991. PLEASE |
| CLARIFY IF THE PROJECT IS A BATHTUB TO SHOWER |
| CONVERSION OR AN EXISTING SHOWER UPGRADE. A BATHTUB TO |
| SHOWER CONVERSION SHALL COMPLY WITH ITEMS #2 & 3 BELOW. |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. |
| |
| 2) REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL AND |
| PROVIDE A DRAWING FOR THE BATHROOM THAT SHOWS THE |
| DIMENSIONS OF THE SHOWER AND THE REQUIRED 30X48-INCH |
| CLEAR FLOOR SPACE DIAGRAM POSITIONED PARALLEL TO THE |
| SHOWER AND FLUSH WITH THE CONTROL WALL. PLEASE NOTE IF |
| THE SHOWER IS THE ONLY BATHING FIXTURE IN THE CONDO IT |
| SHALL BE MINIMUM 36X36-INCHES IN SIZE. IT IS ALSO |
| REQUIRED THAT NO OTHER FIXTURES SHALL OBSTRUCT THE |
| CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER WITH THE |
| EXCEPTION OF A LAVATORY WHICH MAY OVERLAP BY 6-INCHES. |
| THE LAVATORY SHALL BE A WALL HUNG WITH KNEE AND TOE |
| CLEARANCES OR HAVE A REMOVABLE CABINET. |
| |
| 3) PROVIDE AN ELEVATION DETAIL FOR THE SHOWER THAT |
| SHOWS THE LOCATIONS OF REQUIRED GRAB BAR REINFORCEMENTS |
| IN ACCORDANCE WITH PAGE 6.13. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |