2023-02-21 11:57:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF "REPLACEMENT OF 2 COMMON |
| DOOR" ON THE APPLICATION; HOWEVER, THERE IS NO |
| INDICATION OF A DETAILED SCOPE OF WORK AND THERE ARE 3 |
| DOORS INDICATED ON THE SITE PLAN |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PLEASE PROVIDE A DETAILED SCOPE OF WORK AND CLARIFY THE |
| NUMBER OF DOORS. |
| |
| |
| |
| 1A) PER SCOPE OF WORK COMMENT ABOVE, PLEASE PROVIDE ALL |
| APPLICABLE DOOR SCHEULE INCLUDING, BUT NOT LIMITED TO, |
| DOOR SPECS, REQUIRED FIRE RATINGS, LOCK/LATCHING |
| HARDWARE, ETC. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| SHOULD THE EXISTING DOOR AND HARDWARE IS EXXISTING AND |
| WILL BE REPLACED WITHIN THE NEW DOOR FRAME, PLAESE |
| INDICATE SUCH. |
| |
| OTHERWISE PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE |
| DETAILS. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |