Plan Review Notes For Permit 23010579 |
Permit Number |
23010579 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-03 13:20:28 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL30310-R2 COVERS MULTIPLE PRODUCTS & | | INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION | | METHOD TO BE USED. ALL APPLICABLE DETAILS AND | | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT | | APPROVAL DRAWINGS. | | 2. FBC R 301 FAC9N-3 SUBMITTED STATE OF FLORIDA PRODUCT | | APPROVAL FL15216-R11 COVERS MULTIPLE INSTALLATION | | METHODS. INDICATE INSTALLATION METHOD ON SECTION 6.3 | | PAGE #4. PLEASE NOTE: LAST LINE OF PARAGRAPH 6.3.1.1; | | FBC REQUIREMENTS TAKES PRECEDENCE OVER MANUFACTUER???S | | INSTALLATION INSTRUCTIONS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|