Plan Review Notes For Permit 23010492 |
Permit Number |
23010492 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-23 06:56:32 | BUILDING REVIEW DENIED: | | | | | | | | 1.) BUILDING REVIEW APPROVAL IS ALSO PENDING APPROVAL | | OF SIGNATURE REVIEW. | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | THE ARCHITECT'S SIGNATURE ON PLAN SHEET A-1 DOES NOT | | APPEAR TO BE 3RD PARTY VERIFIABLE. | | | | A.) DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND | | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | VALID DIGITAL SIGNATURE. | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | 61G1???16 AND 61G15, F.A.C. | | | | B.) SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | 481, F.S. & 61G1. |
|