Plan Review Notes
Plan Review Notes For Permit 23010460
Permit Number 23010460
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-17 15:40:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010460 2000 PALM BEACH LAKES BLVD # 100
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PLEASE PROVIDE OVERVIEW OF BUILDING SHOWING
 LOCATIONS AND ROUTING/ACCESS TO COMMON RESTROOMS AND
 DRINKING FOUNTAIN. INCLUDE ACCESSIBILITY. FBC PL 403.1,
 403.3.3, 403.5, FBC ACC 202.4
  
 2. P0.1/ IWH PUBLIC LAVATORY DETAIL: DETAIL DOES NOT
 ADDRESS HOT/TEMPERED WATER TO SINKS. PROVIDE AND
 SPECIFY A TEMPERATURE-ACTUATED MIXING VALVE CONFORMING
 TO ASSE 1017 AT EACH WATER HEATER SERVICING THE SINKS.
 FBC PL 607.1.1, 613.1
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved