Plan Review Notes
Plan Review Notes For Permit 23010460
Permit Number 23010460
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-17 14:21:281ST REVIEW FMC
 PERMIT: 23010460
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1 UNDER THE HEAT PUMP SCHEDULE LISTS THE
 OUTDOOR AIR BEING SUPPLIED BY EACH WSHP. PROVIDE THE
 OUTDOOR AIR CALCULATIONS FOR EACH USE OF SPACE IN THIS
 TENANT SPACE.
  
 2) SHEET M2.1: SHOWS A 12 X 12 OUTDOOR AIR DUCT. NOTE 2
 INDICATES THAT THIS DUCT WORK TO BE ROUTED BACK TO
 EXISTING MECHANICAL ROOM. PROVIDE DETAIL DRAWINGS FOR
 WHERE THIS DUCT IS LOCATED IN THE MECHANICAL ROOM. IS
 THIS OUTDOOR AIR CONDITIONED BEFORE IT ENTERS THE
 TENANT SPACE? IF NOT PROVIDE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS THAT SHOW THIS UNCONDITIONED AIR
 BEING BROUGHT INTO THIS TENANT SPACE UNTREATED. SHOW
 THAT THE WSHP???S WERE SIZED WITH THIS DESIGN IN MIND
 AS THIS IS NOT THE TYPICAL INSTALLATION. FBC 107.3.5
  
 3) PLEASE SHOW THE SMOKE DETECTION SYSTEM FOR THESE
 WSHP IN THE TENANT SPACE. FMC 606.2.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  