2023-01-17 14:21:28 | 1ST REVIEW FMC |
| PERMIT: 23010460 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M6.1 UNDER THE HEAT PUMP SCHEDULE LISTS THE |
| OUTDOOR AIR BEING SUPPLIED BY EACH WSHP. PROVIDE THE |
| OUTDOOR AIR CALCULATIONS FOR EACH USE OF SPACE IN THIS |
| TENANT SPACE. |
| |
| 2) SHEET M2.1: SHOWS A 12 X 12 OUTDOOR AIR DUCT. NOTE 2 |
| INDICATES THAT THIS DUCT WORK TO BE ROUTED BACK TO |
| EXISTING MECHANICAL ROOM. PROVIDE DETAIL DRAWINGS FOR |
| WHERE THIS DUCT IS LOCATED IN THE MECHANICAL ROOM. IS |
| THIS OUTDOOR AIR CONDITIONED BEFORE IT ENTERS THE |
| TENANT SPACE? IF NOT PROVIDE THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS THAT SHOW THIS UNCONDITIONED AIR |
| BEING BROUGHT INTO THIS TENANT SPACE UNTREATED. SHOW |
| THAT THE WSHP???S WERE SIZED WITH THIS DESIGN IN MIND |
| AS THIS IS NOT THE TYPICAL INSTALLATION. FBC 107.3.5 |
| |
| 3) PLEASE SHOW THE SMOKE DETECTION SYSTEM FOR THESE |
| WSHP IN THE TENANT SPACE. FMC 606.2.2 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |