Plan Review Notes For Permit 23010460 |
Permit Number |
23010460 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-25 12:59:09 | ELECTRIC REVIEW FAILED | | 1) PLEASE INDICATE BY NOTE, ON ELECTRICAL PLANS, | | CLASSIFICATION OF FACILITY AS A MEDICAL OFFICE, | | AMBULATORY OR NON- AMBULATORY HEALTH CARE OCCUPANCY, AS | | DEFINED BY NEC 517.2 DEFINITIONS | | 2) PLEASE INDICATE AND DETAIL ON ELECTRICAL PLANS | | COMPLIANCE WITH ALL APPLICABLE ELECTRICAL REQUIREMENTS | | AS DETAILED BY NEC ARTICLE 517 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|