2023-04-07 13:46:45 | 1ST REVIEW FMC |
| PERMIT: 23010434 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE BATHROOM EXHAUST SHALL MEET FMC TABLE 403.3.1.1 |
| WHICH IS 50 CFM PER WATER CLOSET OR URINAL IF THE FAN |
| RUNS CONTINUOUSLY WHILE OCCUPIED OR 70 CFM PER WATER |
| CLOSET OR URINAL IF THE FAN RUNS INTERMITTENTLY. PLEASE |
| SPECIFY THE DESIGN OF THE EXHAUST FAN FOR THE |
| BATHROOMS. ALSO, THE CFM???S REQUIRED IF THE FAN RUNS |
| CONTINUOUSLY IS 750 CFM. EF-2 IS 700 CFM PLEASE MAKE |
| SURE THE EF-2 MEETS THE MINIMUM EXHAUST REQUIREMENTS |
| FOR THE BATHROOM EXHAUST. |
| |
| 2) THIS COMMENT WAS NOT ADDRESSED IN THE FIRST CYCLE |
| RESUBMITTAL: PROVIDE DETAILS FOR THE WARMING KITCHEN, |
| INCLUDE ALL COOKING AND WARMING APPLIANCES. FBC 107.3.5 |
| |
| 3) THE OUTDOOR AIR CALCULATION SHOULD BE ADJUSTED FOR |
| THE CORRECTED OCCUPANT COUNT TAKEN FROM FMC TABLE |
| 403.3.1.1 AND NOT THE ARCHITECT???S OCCUPANT COUNT. FMC |
| 403.3.1.1 3RD SENTENCE. |
| |
| CLASSROOM SHOULD BE 8 OCCUPANTS |
| MULTIPURPOSE ASSEMBLY SHOULD BE 66 OCCUPANTS |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |