Review Stop M
Sequence Number 2
Notes
Date Text
2023-04-07 13:46:451ST REVIEW FMC
 PERMIT: 23010434
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BATHROOM EXHAUST SHALL MEET FMC TABLE 403.3.1.1
 WHICH IS 50 CFM PER WATER CLOSET OR URINAL IF THE FAN
 RUNS CONTINUOUSLY WHILE OCCUPIED OR 70 CFM PER WATER
 CLOSET OR URINAL IF THE FAN RUNS INTERMITTENTLY. PLEASE
 SPECIFY THE DESIGN OF THE EXHAUST FAN FOR THE
 BATHROOMS. ALSO, THE CFM???S REQUIRED IF THE FAN RUNS
 CONTINUOUSLY IS 750 CFM. EF-2 IS 700 CFM PLEASE MAKE
 SURE THE EF-2 MEETS THE MINIMUM EXHAUST REQUIREMENTS
 FOR THE BATHROOM EXHAUST.
  
 2) THIS COMMENT WAS NOT ADDRESSED IN THE FIRST CYCLE
 RESUBMITTAL: PROVIDE DETAILS FOR THE WARMING KITCHEN,
 INCLUDE ALL COOKING AND WARMING APPLIANCES. FBC 107.3.5
  
 3) THE OUTDOOR AIR CALCULATION SHOULD BE ADJUSTED FOR
 THE CORRECTED OCCUPANT COUNT TAKEN FROM FMC TABLE
 403.3.1.1 AND NOT THE ARCHITECT???S OCCUPANT COUNT. FMC
 403.3.1.1 3RD SENTENCE.
  
 CLASSROOM SHOULD BE 8 OCCUPANTS
 MULTIPURPOSE ASSEMBLY SHOULD BE 66 OCCUPANTS
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  