Plan Review Notes
Plan Review Notes For Permit 23010434
Permit Number 23010434
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-03 13:37:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010434
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 POTABLE WATER SERVICE BACKFLOW PREVENTER AND THE PERMIT
 APPLICATION FOR THE DEVICE SHALL BE SUBMITTED PRIOR TO
 PLUMBING PLAN APPROVAL FOR THE BUILDING. YOU CAN SUBMIT
 AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT
 HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) PLEASE NOTE SEPARATE PERMITS ARE REQUIRED FOR BOTH
 THE IRRIGATION SYSTEM AND THE SYSTEM BACKFLOW
 PREVENTER, HOWEVER THESE PERMITS MAY BE SUBMITTED AT A
 LATER DATE AND WILL NOT IMPACT ISSUANCE OF THE MAIN
 BUILDING PERMIT- SECS. 105.1 & 107.2.1 WPB.
  
 3) SHEETS P2.1.0 & P.2.2.0: PLEASE CORRECT THE SANITARY
 VENTING PER ITEMS A & B- FBC P.
  
 A) THE EWC1 FIXTURE DRAIN CANNOT BE VENTED BY THE L1
 COMMON DRY VENT FOR THE BATHROOM HORIZONTAL WET VENT
 SYSTEM- SECS. 912.1 & 912.2.1. AN INDIVIDUAL VENT IS
 REQUIRED FOR THE EWC1 AND THE FIXTURE DRAIN SHALL
 CONNECT TO THE BUILDING DRAIN DOWNSTREAM OF THE
 BATHROOM HORIZONTAL WET VENT CONNECTION.
  
 B) THE FIXTURE DRAIN FOR SH1 IN WOMEN'S SHOWER IS NOT
 BEING VENTED BY THE BATHROOM WET VENT BRANCH UPSTREAM
 OF IT AND IS MAKING AN INDIVIDUAL CONNECTION TO THE
 BUILDING DRAIN. EITHER RELOCATE THE DRAIN CONNECTION TO
 THE BRANCH DRAIN OR PROVIDE AN INDIVIDUAL VENT- SECS.
 910.1 & 912.1.
  
 4) P2.1.0 & P.2.2.0: PROVIDE TRAP SEAL PROTECTION FOR
 THE FLOOR DRAINS- SEC. 1002.4.1.1 FBC P.
  
 5) P2.1.0 & P.2.2.0: SHOW THE LOCATION OF THE REQUIRED
 EWH THERMAL EXPANSION CONTROL DEVICE AND PIPING
 CONNECTION- SEC. 607.3 FBC P.
  
 6) P2.1.0 & P2.2.0: DETAIL EWH RELIEF VALVE DISCHARGE
 SYSTEM- DISCHARGE PIPE, PAN, PAN DRAIN PIPE, AND DRAIN
 TERMINATION LOCATION- SECS. 504.4- 504.7.2 FBC P.
  
 7) P2.0.0: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 MASTER THERMOSTATIC MIXING VALVE- SEC. 607.1.1 & 613.1
 FBC P.
  
 8) P2.1.0 & P.2.2: INDICATE THE MEANS OF PROVIDING
 TEMPERED WATER DELIVERY FROM THE PUBLIC LAVATORIES-
 SEC. 419.5 FBC P. PLEASE NOTE TEMPERED WATER MIXING
 VALVES SHALL CONFORM TO ASSE 1070- SEC. 607.1.2 FBC P.
  
 9) P2.1.0 & P.2.2: THE 1/2-INCH FIXTURE SUPPLY PIPES TO
 THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE
 LENGTHS BASED ON TABLE C404.5.1 FBC ENERGY. PROVIDE
 EITHER A RECIRCULATION PUMP FOR THE SYSTEM WITH
 RECIRCULATION LOOPS TO THE LAVS, OR POINT OF USE WATER
 HEATERS AT EACH LAV LOCATION.
  
 10) SHEETS A-2.1.3, P2.1.0 P.2.2.0: PLEASE PROVIDE ROOF
 DRAINAGE GPM FLOW CALCULATIONS BASED ON THE RATE FALL
 RATE AND ROOF SQUARE FOOT AREAS- SECS. 1106.1 & 1106.2
 FBC P.
  
 11) P2.1.0: THE PLAN SHOWS A WARMING KITCHEN WITH A
 SINK. PLEASE DETAIL WHAT TYPE OF FOOD PREP OR COOKING
 OPERATIONS WILL BE CONDUCTED IN THE KITCHEN IN ORDER TO
 DETERMINE IF GREASE WASTE REMOVAL WILL BE REQUIRED-
 REFER TO SECS. 1003.3.1 FBC P.
  
 12) A2.1.1 & P2.0.0: THE WIDTHS OF THE STANDARD WATER
 CLOSET COMPARTMENTS SHALL BE 30-INCHES, AND THE DEPTHS
 SHALL BE 60-INCHES FOR FLOOR MOUNTED WATER CLOSETS-
 SEC. 405.3.1 FBC P. THE FLOOR PLAN DOES NOT PROVIDE THE
 WIDTH MEASUREMENTS AND THE DEPTHS ARE UNDERSIZED AT
 4FT. 6-INCHES.
  
 13) A2.1.1: PLEASE SHOW THE DEPTHS OF THE MEN'S AND
 WOMEN'S SHOWERS- SEC. 608.2.2 FBC ACC.
  
 14) A2.1.1 & A2.4.1: PLEASE SHOW THE CENTERLINE
 MEASUREMENTS OF THE ACCESSIBLE WATER CLOSETS FROM THE
 ADJACENT SIDE WALLS- SEC. 604.2 FBC P.
  
 15) A2.1.1, A2.4.1: PLEASE SHOW THE HEIGHTS OF THE
 ACCESSIBLE WATER CLOSET SEATS FROM THE FINISHED FLOORS-
 SEC. 604.4 FBC ACC.
  
 16) A2.4.1 DETAIL 2: IT APPEARS THE SHOWER SPRAY HANDLE
 IS LOCATED ABOVE THE MAXIMUM 48-INCHES HEIGHT ALLOWABLE
 PER SEC. 608.5.2 FBC ACC.
  
 17) A2.4.1: THE DRINKING FOUNTAINS APPEAR TO BE
 PROTRUDING INTO THE CIRCULATION PATH WHICH IS NOT IN
 COMPLIANCE WITH SEC. 307.2 FBC ACC.
  
 18) A2.4.1: PLEASE DETAIL ACCESSIBLE DRINKING FOUNTAIN
 COMPLIANCES PER ITEMS A, B, & C- FBC ACC.
  
 A) CLEAR FLOOR SPACE APPROACH DIAGRAM AND DIMENSIONS
 FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN - SEC. 602.2.
  
 B) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE FOUNTAIN- SEC. 602.2.
  
 C) SPOUT HEIGHTS FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN
 AND THE FOUNTAIN FOR STANDING PERSONS- SEC. 602.4 &
 602.7.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  