2023-06-29 10:34:11COMMUNITY CENTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PAGE 6 OF THE THRESHOLD INSPECTOR FORM WHICH IS
 SIGNED AND SEALED BY THE THRESHOLD INSPECTOR - DOES NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 I CHECK THE ELECTRONIC SIGNATURE BY OPENING THEM IN
 ???ADOBE READER???. THE ???ADOBE READER??? STATES
 WHETHER THEY ARE AN ORIGINAL ELECTRONICALLY SIGNED
 DOCUMENT. WHEN ELECTRONICALLY SIGNED DRAWINGS ARE
 PRINTED OUT, THEY LOSE THEIR ELECTRONIC SIGNATURE.
 ELECTRONICALLY SIGNED DRAWINGS NEED TO BE MOVED AROUND
 IN THE COMPUTER FROM PLACE TO PLACE. FROM THE
 ARCHITECT???S OR ENGINEER???S COMPUTER TO YOUR COMPUTER
 TO THE CITY???S ELECTRONIC PLAN REVIEW (PROJECTDOX).
 MAYBE YOURS WERE PRINTED OUT AT SOME TIME?
  
 2) PAGE 8 OF THE THRESHOLD INSPECTOR FORMS "GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS AND RESIDENT INSPECTORS" WHICH IS FOR THE
 CONTRACTORS SIGNATURE WILL BE REQUIRED WHEN THE
 CONTRACTOR IS CHOSEN.
  
  
  