2023-02-22 06:48:30 | 1ST REVIEW FMC |
| PERMIT: 23010432 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| 1) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT |
| THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A |
| SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT |
| WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| |
| 2) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1 |
| |
| 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FEC C403.2.1 |
| |
| 4) ADD A NOTE ON THE DRAWING THAT THIS BUILDING WILL |
| NEED TO MEET THE COMMERCIAL BUILDING COMMISSIONING |
| REQUIREMENTS OF FEC C408. FEC C401.2.1 |
| |
| 5) SHEET M1.0.1: PLEASE UPDATE THE MULTIPURPOSE |
| ASSEMBLY OCCUPANCY OUTDOOR AIR CFM???S FOR RTU-1. DOING |
| THE CALCULATION USING THE OCCUPANCY DENSITY FROM TABLE |
| 403.3.1.1 FOR THE 1580 SQ. FT. I GET 190 OCCUPANTS. |
| THIS INCREASES THE OUTDOOR AIR FOR THIS AREA TO 1045 |
| CFM???S. |
| |
| 6) SHEET M1.0.1: RTU-5; THE MULTIPURPOSE ASSEMBLY AREA |
| WOULD HAVE 216 OCCUPANTS WITH A TOTAL OF 1188 CFM???S |
| OF OUTDOOR AIR REQUIRED FOR THIS SPACE. |
| |
| 7) SHEET M1.0.1: RTU-5; THE KITCHEN COOKING AREA IS |
| MISSING THE PEOPLE BREATHING ZONE PART OF THE EQUATION. |
| MINIMUM OF 12 PEOPLE FOR THIS AREA AND A TOTAL OF |
| OUTDOOR AIR IS 157 CFM???S REQUIRED. |
| |
| 8) SHEET M1.2.1: THE RETURN IN THE KITCHEN WILL NEED TO |
| MEET THE 10 FEET FROM THE HOOD REQUIREMENT IN FMC 601.5 |
| 2ND EXCEPTION NUMBER 1. |
| |
| 9) SHEET M1.2.1: PLAN NOTE 4 INDICATES AN EXHAUST FAN |
| EF 1-5, THIS EF 1-5 IS NOT ON THE EXHAUST FAN SCHEDULES |
| ON SHEET 1.0.1. |
| |
| 10) SHEET M1.2.1: PLAN NOTE 3 INDICATES AN EXHAUST FAN |
| EF 1-6, THIS EF 1-6 IS NOT ON THE EXHAUST FAN SCHEDULES |
| ON SHEET 1.0.1 |
| |
| 11) ALL MECHANICAL EQUIPMENT ON THE ROOF WILL NEED TO |
| MEET THE 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARD |
| PROTECTION ACCORDING TO FMC 304.11 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |