2023-01-30 16:10:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010432 1501 N AUSTRALIAN AVE
  
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
  
 A. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
  
 1. INDICATE ON THE PLANS THE TYPE OF GAS; NATURAL OR
 LP.
  
 2. INCLUDE ON THE RISER DIAGRAM THE FOLLOWING:
 ***A) LOCATIONS OF VALVES (INCLUDING EMERGENCY SHUTOFF
 VALVE) AND REGULATORS; FBC FG 401.1
 ***B) SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN
 REGULATORS; FBC FG 402.1
 ***C) INCLUDE PIPE LENGTHS, APPLIANCE ID, BTU LOADS,
 MATERIALS AND DISTANCES TO THE APPLIANCES THAT WERE
 USED TO CALCULATE MINIMUM PIPE SIZES USING THE SIZING
 TABLES FROM FBC FG 402.4; INCLUDE REFERENCES TO THE
 SPECIFIC TABLE(S). FBC FG 402.4.1, 402.4.2, 402.4.3
  
 3. PROVIDE AN EQUIPMENT SCHEDULE; LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
  
 4. PROVIDE ON FLOOR PLAN THE ID AND LOCATION OF
 APPLIANCE AND CORRESPONDING BTU LOAD.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 COOKING LINE AND SHOW HOW IT IS PROVIDED. FBC FG 304.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  